5.3.19 Concrete Mix Proportioning and Strength Acceptance

Construction monitoring is the geotechnical consultant's final opportunity to verify that subsurface conditions match design assumptions, that materials meet…
Authors: Daniel P. Colwell and Mario Ruel
5.3.19 Concrete Mix Proportioning and Strength Acceptance

Culvert headwalls, wall caps, drainage structures and drilled shafts all bring concrete into a geotechnical project, and the geotechnical engineer is often the one in the field when the cylinder results come back. The PCA's Design and Control of Concrete Mixtures sets out the ACI 318 sequence. A mix is proportioned for a required average strength f'cr, which is higher than the specified f'c by a margin that depends on how variable the producer's results have been. Strength tests are then judged on running averages of three, not on single cylinders. Bungey's Testing of Concrete in Structures covers what to do when the cylinders fail: cores, rebound hammer and pulse velocity, and how much weight each deserves.

5.3.19.1 Criteria

Equation 5.3-3. Required average strength (ACI 318), f'c ≤ 5000 psi

f'cr = the larger of f'c + 1.34s and f'c + 2.33s − 500  (psi)
Table 5.3-10. Strength margins and acceptance limits
ConditionRequirement
Standard deviation s from 15, 20 or 25 testsMultiply s by 1.16, 1.08 or 1.03 (1.00 at 30 or more)
No test record, f'c under 3000 psif'cr = f'c + 1000
No test record, f'c 3000 to 5000 psif'cr = f'c + 1200
No test record, f'c over 5000 psif'cr = 1.1f'c + 700
Acceptance of strength testsEvery average of 3 consecutive tests ≥ f'c, and no single test more than 500 psi below f'c (10% below when f'c exceeds 5000)
Cores in suspect concreteAverage of 3 cores ≥ 85% of f'c and no core below 75%
Sampling frequency (one railroad's general specification)One set per day's pour, plus one set for each 50 cu yd beyond the first 50 cu yd of a class; one 7-day cylinder per set
Table 5.3-11. Maximum water-cementitious ratio for strength (ACI PRC-211.1-22, as tabulated by PCA)
28-day strength (psi)Non-air-entrainedAir-entrained
20000.820.74
30000.680.59
40000.570.48
50000.480.40
60000.410.32
70000.33–

The calculator interpolates for f'cr and takes the lower of this value and the durability limit. PCA's own worked example reads w/cm from a material-specific trial-batch curve, so it differs from the table; use trial batches where they exist.

5.3.19.2 Worked example

For a 4000 psi air-entrained mix from a producer with s = 300 psi over 30 tests, f'cr = max(4000 + 1.34×300, 4000 + 2.33×300 − 500) = 4,402 psi, matching PCA's example. The table gives w/cm 0.45 for that strength, which controls over a 0.50 exposure limit. A 120 cu yd pour in one day needs 3 sets of cylinders. The eight sample results average 4,168 psi: every running average of three meets 4000 psi and no test falls below 3500 psi, so the concrete is accepted even though two single results are below f'c. With no test record the same mix would have to be proportioned for 5,200 psi.

A low single cylinder is not a failed structure. Check the test first (capping, curing, handling), then the running average. Core only when the acceptance criteria are actually missed. Bungey stresses that in-place concrete is expected to be weaker than standard-cured specimens, which is why cores are judged against 85% of f'c and not f'c itself.

Open the concrete acceptance calculator →
Required average strength, w/cm for strength and durability, the number of cylinder sets per pour, running-average and single-test acceptance, and core acceptance.

5.3.19.3 Sources in the library

These documents are in the reference library. The summaries above are paraphrased; equations and tabulated limits are standard or published values. Individual railroads, clients and projects are not named.

  • S.H. Kosmatka and M.L. Wilson, Design and Control of Concrete Mixtures, 15th edition (Portland Cement Association): required average strength, the w/cm table, proportioning steps and acceptance criteriaFind source ↗
  • J.H. Bungey, Testing of Concrete in Structures, 3rd edition: cores, in-place tests and interpreting low resultsFind source ↗
  • P. Domone and J. Illston (eds.), Construction Materials: Their Nature and Behaviour, 4th edition: hydration, strength development and durability of concreteFind source ↗
  • A Class I railroad's general construction specifications (concrete, Section 3.09 to 3.11): sampling frequency, cylinder sets, acceptance and testing-laboratory reportingFind source ↗