The three examples cover a cantilever wall, an MSE wall and the seismic case for a gravity wall. Each is laid out as Given, Required, Equations, a flow chart of the steps with a spot check at each, and the Solution. Walls that retain track next to an operating line are usually soldier pile and lagging; Section 7.1.3.1 works that case.
Example 7.1-1: Cantilever Wall at a Rock Cut Transition
A second main track on a Class I railroad located in the Shenandoah Valley of western Virginia needs a 20-ft cantilever wall where the slope is cut back. The example computes the earth pressure with Coulomb wall friction, adds the train surcharge, and checks sliding and overturning on a trial footing.
ΣMR ≈ 142,000 (from the revised geometry) / 67,060
FS = 2.12 ≥ 2.0
↓
Solution
KA = 0.254; sliding 1.58; overturning needs B = 14 ft.
Solution
KA = 0.254 and the total thrust is 8,738 lb/ft. Sliding passes at 1.58; overturning fails at B = 10 ft (1.43) and passes at B = 14 ft (2.12).
Cantilever walls usually take three to five geometry iterations; the heel is the most effective thing to lengthen because it adds both soil weight and lever arm. The uniform 520-psf surcharge understates the load where the track is close to the wall, so recheck sliding and overturning with the strip load (Section 7.1.3.1) once the track offset is fixed. Railroad walls next to track are usually soldier pile and lagging; a cantilever wall suits a cut transition like this one.
Example 7.1-2: MSE Wall at an Intermodal Yard Throat
A 30-ft MSE wall supports an approach embankment at an intermodal expansion on a Class I railroad located in Kansas City. Each geogrid layer must carry the horizontal earth pressure over its tributary spacing, and must be anchored far enough behind the failure surface not to pull out.
Given and required for Example 7.1-2.
Given
Variable
Value
Description
H
30 ft
Reinforced fill
φ′ = 36°, γ = 125 pcf
Geogrid
Sv = 2.0 ft; Rc = 1.0; Le = 4.5 ft at z = 28 ft
F*, α, C
0.67 tanφ′ = 0.487; 0.8; 2
FHWA GEC 11 defaults for geogrid
q
520 psf
Train surcharge
L
22 ft
Reinforcement length
qallow
6,000 psf
Foundation
Required
Maximum reinforcement load at z = 28 ft
Pullout factor of safety
Bearing pressure
Equations
Eq. 1: KA = tan²(45° − φ′/2) — Rankine
Eq. 2: σh = KA(γz + q); Tmax = σh Sv
Eq. 3 (FHWA GEC 11): Pr = F* α σ′v Le C Rc — pullout resistance per unit width; C = 2 for geogrid (both faces); α = 0.8 for geogrid
Tmax = 2,090 lb/ft at z = 28 ft; pullout FS = 5.9; bearing 4,270 psf against 6,000 psf allowable.
The geogrid must also have a long-term design strength Tal above 2,090 lb/ft after the reduction factors for creep, installation damage and durability (FHWA GEC 11); that comes from the product data. The final design must also check eccentricity of the base reaction, global stability and settlement.
Example 7.1-3: Seismic Earth Pressure on a Gravity Wall
A 15-ft gravity wall on a Class I railroad located near Salem, Oregon, in Seismic Design Category D. The Seed-Whitman simplification adds a seismic increment to the static thrust and applies it higher on the wall, which is why seismic overturning so often governs.
Given and required for Example 7.1-3.
Given
Variable
Value
Description
H
15 ft
Backfill
φ′ = 32°, γ = 120 pcf
kh, kv
0.25 and 0
KA
0.307 (Rankine)
Coulomb with δ = 21.3° gives 0.275
Target
FSOT ≥ 1.1 seismic (assumed)
Required
Seismic thrust and increment
Seismic overturning moment
Equations
Eq. 1: ΔKAE ≈ ¾ kh; KAE = KA + ΔKAE — Seed and Whitman (1970), φ′ 30° to 40°, kh < 0.3
Eq. 2: P = ½KγH²
Eq. 3: M = PA(H/3) + ΔPAE(0.6H)
Steps
Step 1 · KAE (Eq. 1)
0.307 + 0.75 × 0.25
0.495
Spot check: The full Mononobe-Okabe solution with δ = 21.3° gives 0.476, so the simplified value is slightly conservative.
↓
Step 2 · Forces (Eq. 2)
½ × 0.495 × 120 × 225; ½ × 0.307 × 120 × 225
PAE = 6,683; PA = 4,150; ΔPAE = 2,532 lb/ft
↓
Step 3 · Moment (Eq. 3)
4,150 × 5.0 + 2,532 × 9.0 = 20,750 + 22,790
M = 43,540 ft-lb/ft, 2.1 times the static moment
↓
Solution
Seismic overturning moment 2.1 times the static.
Solution
KAE ≈ 0.495; the seismic increment is 2,532 lb/ft, and the seismic overturning moment is about 43,500 ft-lb/ft, 2.1 times the static value.
The increment acts at 0.6H rather than H/3, so it nearly doubles the moment on its own. In Seismic Design Category D the seismic case usually governs the wall geometry; size the footing for FSOT ≥ 1.1 under this moment.