7.1.6 Drainage Behind Retaining Walls

Retaining structures are among the most consequential geotechnical elements in railroad capital programs.
Authors: Daniel P. Colwell and Mario Ruel
7.1.6 Drainage Behind Retaining Walls

Hydrostatic pressure behind a wall can double or triple total lateral force. Drainage is not optional — it is a fundamental design requirement.

Hydrostatic Pressure — Increase with Depth
Hydrostatic Pressure — Increase with Depth
Permeability vs Drainage
Permeability vs Drainage

Hydrostatic pressure added to active pressure:

σ_w = γ_w × h_w (psf)

where h_w = height of water behind wall (ft); γ_w = 62.4 pcf.

Design requirement: All walls retaining granular fill must include continuous granular drainage blanket (≥ 12 in. thick, AASHTO No. 57 stone or equivalent), perforated pipe collector drain at the base, and weep holes through the wall face (4 in. diameter minimum, spaced ≤ 10 ft, per AREMA Ch. 8).

For walls in cold regions where freeze-thaw cycles are severe, insulated drainage blankets or thermally protected drains are needed to prevent pipe freeze.

Supplemental reference

Why segmental (block-faced) geosynthetic walls fail: backfill and inspection

A Geosynthetic Research Institute review estimated about 35,000 geosynthetic-reinforced MSE walls, about 30% of them block-faced SRWs. It examined 26 problem walls (12 serviceability, 14 collapses). In 25 of 26 the cause was poor backfill or poor construction and/or lack of inspection, and 20 of 26 had silt or clay backfill in the reinforced zone. The collapse mechanism was hydrostatic pressure: a crack admits water, the facing bulges, a block is dislodged, and the blocks above follow progressively until the facing and drainage gravel are lost.

SieveKoerner (1994)FHWA (1998)NCMA (1997)
No. 410010020–100
No. 400–600–600–60
No. 20000–150–35

Recommended reinforced-backfill gradations, % passing (GRI compilation).

Recommendations: prefer sand in the reinforced zone (gravel is acceptable but costs more and increases installation damage). If silt or clay is used it must be drained internally and externally, with particular attention to surface drainage. Design for hydrostatic pressure from all sources and directions. Suggested construction QA presence is 67% of construction time for noncritical permanent walls and 100% for critical walls; critical walls next to track should have full-time inspection. The same survey (1998 bid prices from 40 state DOTs) found geosynthetic MSE the least-cost wall type in every height class.

Source: Geosynthetic Research Institute (c. 2000). Geosynthetic Reinforced Segmental Retaining Walls (SRWs) (presentation; cost survey after J. Koerner et al., 1998)