For facilities in northern climates, frost penetration depth Z_f (ft) is estimated using the modified Berggren equation:
Where:
Z_f is in feet. The full modified Berggren equation multiplies the right-hand side by the correction coefficient λ (≤ 1, from the thermal ratio and fusion parameter), so this simplified form is conservative (deeper).

Source: Aldrich, H.P. and Paynter, H.M. (1953), Analytical Studies of Freezing and Thawing of Soils, ACFEL Tech. Rep. 42; UFC 3-130-06 / TM 5-852-6, Calculation Methods for Determination of Depths of Freeze and Thaw in Soils; Pavement Interactive, "Modified Berggren Formula."
Design freezing indices by location (99% confidence level):
| Location | Design F_I (°F-days) | Typical Z_f (ft) |
|---|---|---|
| Winnipeg, MB | 3,800 | 7.5–9.0 |
| Edmonton, AB | 3,200 | 6.5–8.0 |
| Thunder Bay, ON | 3,000 | 6.0–7.5 |
| Chicago, IL | 1,200 | 3.5–4.5 |
| Minneapolis, MN | 1,800 | 4.5–5.5 |
| Kansas City, MO | 800 | 2.5–3.5 |
| Atlanta, GA | 150 | 0.5–1.0 |
| Symbol | What it is | Comes from | How to get it | Typical range |
|---|---|---|---|---|
| kf | thermal conductivity of frozen soil (BTU/hr·ft·°F) | Published data | Kersten charts in UFC 3-130-06 (TM 5-852-6) for the measured γd and w. | fine-grained 0.8–1.4 BTU/hr·ft·°F · by USCS group |
| FI | freezing index (°F-days) | Published hazard / climate data | Design freezing index from NOAA climate records per UFC 3-130-06 (average of the 3 coldest winters in 30 years). | project-specific |
| L | volumetric latent heat of fusion (BTU/ft³) | Another equation | Computed: L = 144 × w × γ_d; 144 BTU/lb = latent heat of water | project-specific |
| w | water content (decimal) | Lab test | Oven-dry water content of samples (ASTM D2216); field check by microwave (D4643) or nuclear gauge (D6938). | gravels/sands 3–25%, clays 15–70% · by USCS group |
| γd | dry unit weight (pcf) | Lab or field test | Lab: ASTM D7263 on tube samples. Field: nuclear gauge (ASTM D6938), sand cone (D1556) or drive cylinder (D2937). Or γd = γ/(1 + w). | sands 90–125, clays 80–115 pcf · by USCS group |
Frost susceptibility is classified per the USACE system (modified for pavement applications):
| Group | Frost Susceptibility | Soil Types | Approx. lab heave rate class (in./day) | Design Action |
|---|---|---|---|---|
| NFS | Negligible | Clean gravels and sands (< 3% finer than 0.02 mm) | < 0.02 | No frost protection needed |
| F1 | Low | Gravelly soils with 3–10% finer than 0.02 mm | 0.02–0.08 | Minimal protection; monitor |
| F2 | Medium | Gravelly soils with 10–20% finer than 0.02 mm; sands with 3–15% | 0.08–0.16 | Partial replacement with non-frost-susceptible material |
| F3 | High | Gravelly soils > 20% finer than 0.02 mm; sands > 15% (except very fine silty sands); clays with PI > 12 | 0.16–0.31 | Full replacement to Z_f or frost protection layer |
| F4 | Very High | All silts; very fine silty sands > 15% finer than 0.02 mm; clays with PI < 12; varved clays | > 0.31 | Full replacement; subgrade stabilization; drainage mandatory |
In cold regions, replace F3 and F4 subgrade materials within the frost depth with granular material meeting: P-200 ≤ 3%, CBR ≥ 40%, non-plastic.
During spring thaw, subgrade strength may be reduced to as low as 20–30% of the non-frozen value due to saturated, softened conditions. Owner railroads may apply a seasonal correction factor:
Where f_thaw = 0.20 to 0.35 (conservative range during thaw period). The AASHTO 1993 finds the effective M_r from the average relative damage over the 12 months:
Because u_f rises steeply as M_r falls, the low-strength thaw months govern the design.
| Symbol | What it is | Comes from | How to get it | Typical range |
|---|---|---|---|---|
| fthaw | 0.20 to 0.35 (conservative range during thaw period) | Chart, table or correction factor | Read from the cited chart or table for the site conditions; values listed in the definition. | project-specific |
| Mr | resilient modulus | Lab test (or correlation) | Repeated-load triaxial (AASHTO T 307), or Mr ≈ 2,555·CBR0.64 (MEPDG). | fine-grained 3,000–14,000 psi · by USCS group |
Mauduit, Livet and Piau summarize the French approach, which is useful where track and paved yard areas share frost-susceptible subgrade:
Source: Mauduit, C., Livet, J. and Piau, J-M. (2007). “Frost Design Method for Roadways and Railways – State of the Art in France.” In Gomes Correia, A., Momoya, Y. and Tatsuoka, F. (eds.), Design and Construction of Pavements and Rail Tracks. Taylor & Francis/Balkema
The frost index is the integral of below-freezing temperature over time (°F-days or °F-hours). It is chosen for a design return period: F2, F5, F10 or F100 correspond to a 50%, 20%, 10% or 1% chance of freezing through in a given winter. For track, the required ballast-plus-subballast thickness rises from about 20 in. at 360°F-days to over 6.6 ft at 2,900°F-days, depending on mean annual temperature (Figure 7.3-12). The same chart is a reasonable cross-check for granular protection under yard pavements built on frost-susceptible silts. Chapter 2.3, §2.5 has the full frost discussion.

After Profillidis (2014), §9.11.1, §12.5.2, Table 9.6, Fig. 12.6. Full reference under Supplemental References.
Heave requires saturated soil, frost-susceptible soil (silt), sub-zero temperature, a slowly advancing freezing front, and a water supply from below. Remove any one and it stops. For yards and access roads, that means drainage that keeps the water table down and clean, low-fines granular base. Fines-rich material compacts well dry but heaves and loses strength when wet.
After Geotechnology for Railroaders Program, Module 6.6, Module 2; Module 6.6 §02; Module 2 §09. Full reference under Supplemental References.