Where a design depends on water going into the ground (an infiltration basin, a storm chamber system), measure it. The borehole (single-ring) test below follows a municipal stormwater ordinance procedure that is widely used in the Midwest.
| Step | Requirement |
|---|---|
| Soil boring | Extend at least 5 ft below groundwater; bag samples of each layer between the system bottom and the water table for sieve analysis; density and moisture of each layer; water at drilling and 24 hours; log by USDA texture |
| Test location | At least 5 ft from the boring, or a horizontal distance equal to the depth from test bottom to water table, whichever is greater |
| Setup | Drill to the test depth; push a PVC pipe 3 in. below the bottom; bentonite seal in the annulus; clean, uniform bottom; cap the pipe |
| Pre-soak | Fill the pipe and let it drain to saturate the soil; record the volume added |
| Readings | Record time and depth at intervals that give about 3 in. or less of decline; when within 12 in. of the bottom, refill to 24 in. above the bottom |
| End | Repeat until the rate of decline is constant, then two more cycles |
| Timing | Some agencies do not allow testing within 24 hours after rain |
The ordinance equations assume the wetting front stays above the water table; where it reaches the water table, the equations must be modified, as the worksheet does. Check the field value against grain-size correlations from the sieve analyses; where the correlation gives a higher permeability, the field value is the conservative one to use.
Do not test infiltration where groundwater is within a few feet of the surface; the result is meaningless and the site is not suited to infiltration. One recent client request banned infiltration tests outright for that reason.